Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.3.2.6
4.3.2.7
Table 404:
PDNSPTOC Group settings (Basic)
Parameter
Start value
Operate delay time
404
IECA070698 V1 EN
Figure 209:
Three-phase current quantities during the broken conductor fault in
phase A with the ratio of negative-sequence and positive-sequence
currents

Signals

Table 402:
PDNSPTOC Input signals
Name
I
1
I
2
I_A
I_B
I_C
BLOCK
Table 403:
PDNSPTOC Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
10...100
%
100...30000
ms
Type
Default
Description
SIGNAL
0
Positive sequence current
SIGNAL
0
Negative sequence current
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
1
10
1
100
1MRS758755 A
Description
Start value
Operate delay time
REC615 and RER615
Technical Manual