Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
9.2.6
9.2.7
Table 646:
DCSXSWI Non group settings (Basic)
Parameter
Values (Range)
Identification
REC615 and RER615
Technical Manual
remote and local status indication of, for example, disconnectors, air-break switches
and earthing switches, which represent the lowest level of power switching devices
without short-circuit breaking capability.

Signals

Table 642:
DCSXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
1) Not available for monitoring
Table 643:
ESSXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
1) Not available for monitoring
Table 644:
DCSXSWI Output signals
Name
Type
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
Table 645:
ESSXSWI Output signals
Name
Type
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
Settings
Unit
Step
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Description
Apparatus open position
Apparatus closed position
Apparatus position is ok
Description
Apparatus open position
Apparatus closed position
Apparatus position is ok
Default
Description
DCSXSWI1 switch
Control Object identification
position
Section 9
Control functions
1)
1)
1)
1)