T_DIR function block

Function block

GUID-BD31ED40-3A32-4F65-A697-3E7344730096 V1 EN
Figure 61:
Function block

Functionality

The T_DIR function evaluates enumerated data of the FAULT_DIR data attribute of
the directional functions. T_DIR can only be used with GOOSE. The DIR input can
be connected to the GOOSERCV_ENUM function block, which is receiving the
LD0.<function>.Str.dirGeneral or LD0.<function>.Dir.dirGeneral data attribute sent
by another device.
In case the GOOSERCV_ENUM function block does not receive the value from the
sending device or it is invalid, the default value (0) is used in function outputs.
The outputs FWD and REV are extracted from the enumerated input value.

Signals

Table 70:
T_DIR Input signals
Name
Type
DIR
Enum
Table 71:
T_DIR Output signals
Name
Type
FWD
BOOLEAN
REV
BOOLEAN

T_TCMD function block

Function block
GUID-1CE485AE-2BCA-4D1E-92F5-417340F2589F V1 EN
Figure 62:
Function block
Default
Description
0
Input signal
Default
Description
0
Direction forward
0
Direction backward