Technical Revision History - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 6
Supervision functions
6.3.10
6.4
6.4.1
6.4.2
6.4.3
6.4.4
530

Technical revision history

Table 549:
MDSOPT Technical revision history
Technical revision
B
C
D
Voltage presence PHSVPR
Identification
Description
Voltage presence
Function block
GUID-0205C517-A9C1-4265-990C-7222820EAC1A V1 EN
Figure 276:
Function block
Functionality
The voltage presence function PHSVPR supervises the voltage presence status. The
function can be used for indicating voltage presence status of a load break switch or
a circuit breaker.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of PHSVPR can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Change
Internal improvement.
Internal improvement.
Internal improvement.
IEC 61850
IEC 60617
identification
identification
PHSVPR
PHSVPR
1MRS758755 A
ANSI/IEEE
C37.2 device
number
PHSVPR
REC615 and RER615
Technical Manual