Min3 Function Block - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.16.1.6
126
Table 98:
MAX3 Output signal
Name
OUT
Settings
The function does not have any parameters available in LHMI or PCM600.

MIN3 function block

Function block
GUID-40218B77-8A30-445A-977E-46CB8783490D V1 EN
Figure 70:
Function block
Functionality
The minimum function MIN3 selects the minimum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MIN3 output value is set to 2^21.
Signals
Table 99:
MIN3 Input signals
Name
Type
IN1
FLOAT32
IN2
FLOAT32
IN3
FLOAT32
Table 100:
MIN3 Output signal
Name
OUT
Settings
The function does not have any parameters available in LHMI or PCM600.
Type
FLOAT32
Default
0
0
0
Type
FLOAT32
1MRS758755 A
Description
Output signal
Description
Input signal 1
Input signal 2
Input signal 3
Description
Output signal