Sequence - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
9.4.6.2
REC615 and RER615
Technical Manual
The Auto init parameter defines which INIT_X lines are activated in
the auto-initiation. The default value for this parameter is "0", which
means that no auto-initiation is selected.
A070871 V1 EN
Figure 341:
Example of an auto-initiation sequence with synchronization failure
in the first shot and circuit breaker closing failure in the second shot
In the first shot, the synchronization condition is not fulfilled (SYNC is FALSE).
When the auto wait timer elapses, the sequence continues to the second shot. During
the second reclosing, the synchronization condition is fulfilled and the close
command is given to the circuit breaker after the second reclose time has elapsed.
After the second shot, the circuit breaker fails to close when the wait close time has
elapsed. The third shot is started and a new close command is given after the third
reclose time has elapsed. The circuit breaker closes normally and the reclaim time
starts. When the reclaim time has elapsed, the sequence is concluded successful.

Sequence

The auto reclose sequence is implemented by using CBBs. The highest possible
amount of CBBs is seven. If the user wants to have, for example, a sequence of three
shots, only the first three CBBs are needed. Using building blocks instead of fixed
shots gives enhanced flexibility, allowing multiple and adaptive sequences.
Each CBB is identical. The Shot number CBB_ setting defines at which point in the
auto-reclose sequence the CBB should be performed, that is, whether the particular
CBB is going to be the first, second, third, fourth or fifth shot.
During the initiation of a CBB, the conditions of initiation and blocking are checked.
This is done for all CBBs simultaneously. Each CBB that fulfils the initiation
conditions requests an execution.
The function also keeps track of shots already performed, that is, at which point the
auto-reclose sequence is from shot 1 to lockout. For example, if shots 1 and 2 have
already been performed, only shots 3 to 5 are allowed.
Additionally, the Enable shot jump setting gives two possibilities:
Section 9
Control functions
653