Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
4.6.1.8
4.7
4.7.1
4.7.2
4.7.3
4.7.4
REC615 and RER615
Technical Manual

Monitored data

Table 482:
DPSRDIR Monitored data
Name
Type
ANGLE_RCA
FLOAT32
DPSRDIR
Enum
Multipurpose protection MAPGAPC
Identification
Function description
Multipurpose protection
Function block
GUID-A842A2C8-0188-4E01-8490-D00F7D1D8719 V2 EN
Figure 232:
Function block
Functionality
The multipurpose protection function MAPGAPC is used as a general protection with
many possible application areas as it has flexible measuring and setting facilities. The
function can be used as an under- or overprotection with a settable absolute hysteresis
limit. The function operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself, if desired.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
Protection functions
Values (Range)
Unit
-180.00...180.00
deg
1=on
2=blocked
3=test
4=test/blocked
5=off
IEC 61850
IEC 60617
identification
identification
MAPGAPC
MAP
Section 4
Description
Angle between operating
angle and characteristic
angle
Status
ANSI/IEEE C37.2
device number
MAP
457