Bit No.
from sequence control 1)
from messages [480.7]
from sequence control 1)
from sequence control 1)
from sequence control 1)
from alarm processing [490.4]
from fault processing [490.2]
from alarm processing [490.2]
from alarm processing [490.7]
from fault processing [490.7]
from fault processing
from sequence control 1)
from sequence control 1)
1
2
Status word 2
Meaning
1=Flying restart or excitation active
Bit 16
0=Flying restart not active or excitation finished
Bit 17
Reserve
0=Overspeed
Bit 18
1=No overspeed
1=External fault 1 active
Bit 19
0=No external fault 1
1=External fault 2 active
Bit 20
0=No external fault 2
1=External alarm active
Bit 21
0=No external alarm
1=Converter overload alarm active (A025)
Bit 22
0=No converter overload alarm
1=Converter overtemperature fault active
Bit 23
0=No converter overtemperature fault
1=Converter overtemperature alarm active
Bit 24
0=No converter overtemperature alarm
1=Motor overtemperature alarm active
Bit 25
0=No motor overtemperature alarm
1=Motor overtemperature fault active
Bit 26
0=No motor overtemperature fault
Bit 27
Reserve
1=Motor pulled out/blocked fault active
Bit 28
0=No motor pulled out/blocked fault
1=Bypass contactor energized (only AC units)
Bit 29
0=Bypass contactor not energized
Bit 30
Reserve
1=Pre-charging active
Bit 31
0=Pre-charging not active
3
Status Word 2
r553
Status Word 2
K0033
1
B0132
Fly/Exc active
1
B0136
Overspeed
1
B0138
Ext Fault 1
1
B0140
Ext Fault 2
1
B0142
Ext Warning
1
B0144
Ovld Warn Drive
1
B0146
Tmp Flt Drive
1
B0148
TmpWarn Drive
1
B0150
TmpWarnMotor
1
B0152
TmpFltMotor
1
B0156
Motor blocked
1
B0158
ChrgRelay close
1
B0162
Prechrg active
4
5
V2.4
Display of r553 on the PMU
31 30
2)
B0133
Fly/Exc n.act.
23 22
1)
The sequence control system is the
internal control system (software) for
implementing the drive status (r001).
B0137
No Overspeed
2)
in addition
B0139
No Ext Fault 1
B0141
No Ext Fault 2
B0143
No Ext Warning
B0145
No OvldWarn Drv
B0147
No Tmp Flt Drv
B0149
No TmpWarnDrv
B0151
No TmpWarnMotor
B0153
No TmpFltMotor
B0157
Motor not blocked
B0159
ChrgRelay open
B0163
Prechrg n.act.
6
7
Function diagram
fp_mc_210_e.vsd
MASTERDRIVES MC
08.01.02
n959.28 = 4
29 28
27 26
25 24
21 20
19 18
17 16
Excitation End
B0255
Dependent on P602
8