Communication / CBC
8.4.5.1
Basic parameterization of the units
Basic
parameterization for
MASTERDRIVES
with CUPM, CUMC
or CUVC
Optional boards?
yes
no
P060 = 4
P711 = 0...2000
P712 = 0...2000
P713 = 0...2000
P714 = 1...16
P715 = 0...65535
P716 = 0...2000
P717 = 0...2000
P718 = 0...2000
P719 = 0...2000
P720 = 0...8
P721.01 = 0
P721.02 =
0...65535
P918 = n
P060 = 0
P722 = 0...65535
P053 = x
P060 = 5
8.4-32
Possible optional boards: CBC, CBP, TB
Function selection "hardware configuration"
Basis identifier for PKW task / PKW reply
Basis identifier for PZD-receive
Basis identifier for PZD-send
Number of PZDs for PZD-send
Update rate for PZD-send
Basis identifier for PZD-receive broadcast
Basis identifier for PZD-receive mulitcast
Basis identifier for PZD-receive cross transfer
Basis identifier for PZD-request broadcast
Baud rate
CAN-profile (at the present only 0 possible) (optional)
Bus timing (optional)
CBC bus address (0 ≤ n < 128)
Leave "hardware configuration"
For setting the telegram failure time in ms
(0 = deactivated)
Parameterization enable CBC
Function selection "drive setting"
Fig. 8.4-16
Parameterization of the "hardware configuration" for MASTERDRIVES
with CUPM, CUMC or CUVC