P719 (CB parameter 9)
Binary value for P719
bits 12-15
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0 - 1 1 1 1
If a life guarding event occurs, the converter reacts as configured in P719. An
emergency message with error code 8130 Life Guard Error is also
transmitted.
If P719 is parameterized illegally, error F080 is displayed when the system
exits state 4 "Board configuration" or 5 "Drive setting". Once you have
acknowledged the error, the system returns to the "Board configuration" or
"Drive setting" state where you can correct the faulty parameter assignment.
Example:
A MASTERDRIVES with technology option F01 must be configured as a
CANopen slave. In response to a life guarding event, the drive must
decelerate with OFF 1 and the bus node must not change its status. The
hexadecimal value must be converted to a decimal value and entered in the
parameter.
Bit 12-15 (device
behavior)
Decimal value
Hex value
Param. value
Compendium Motion Control
Communication / CBC CANopen Communication Board
Response to life guarding event
Remains in current state
Shutdown to ready to start
Change to Not Ready to Switch On
Quick stop to Not Ready to Switch On
Reserved / Not permissible
Bit 8-11
(communication
behavior)
1
1
1
1
4545 (11C1 hex)
Bit 0-7 (device
identifier)
193
C1
8.5-25