Siemens SIMOVERT MASTERDRIVES Manual page 1227

Motion control
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

Parameter
Description
P845*
Service parameter, only for Siemens service personnel
SEB AnaOut
Output of connectors to the analog outputs of the SEB
845
Indices 1 - 4 correspond to analog outputs 1 - 4 on the
SEB
Note: If an address is to be output, the parameter value
must be zero before the address is entered in P844.
P846
Service parameter, only for Siemens service personnel
D channels T0
846
P847*
Mode in which the fault counter (in r849) should be used.
Diagnostics
0 Delete all counters and then change over to 1.
847
1 Counters to count up an down. That applies to normal
operation. In the event of a fault, the count is incremented
by 10, and in the event of a valid value the counted is
decremented by 1.
2 Counters to count up only. These can be used to detect
sporadic faults that would otherwise remain undetected.
3 For future use
If a fault counter counts beyond 100, F51 is tripped
provided that fault tripping is implemented in the counter
in question (see r849) and the fault trip is not suppressed
in P848.
P848*
Parameter for suppressing the fult causes given in r849
Config_Diagnos
and alarm A28. The new alarm A28 and fault counter r849
are used for early recognition of latent encoder problems.
848
Each index in P 848 belongs to the corresponding index in
r849.
Setting values:
0: No evaluation! Important, this value may be set only
under exceptional circumstances after consultation with
the hotline, because the fault sources is then
suppressed!!! (Danger!)
1: If the fault count exceeds 100, the appropriate fault is
tripped.
2: Alarm A28 is always set whenever the fault count is
greater than 0.
3: Whenever the fault count exceeds 0, alarm A28 is set.
If the fault count reaches 100, the associated fault is
tripped, in so far as provision for a fault is made in the
software.
Siemens AG
6SE7087-6QX70 (Edition AG)
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
index1: 0
Menus:
Unit: -
- Parameter menu
Indices: 4
- Upread/free access
Type: L2 ,K
Changeable in:
- Ready to switch on
- Operation enabled
Init: 0
Menus:
Min: 0
- Parameter menu
Max: 4
- Upread/free access
Unit: -
Changeable in:
Indices: -
- Ready to switch on
Type: O2
- Operation enabled
Init: 1
Menus:
Min: 0
- Parameter menu
Max: 3
- Upread/free access
Unit: -
Changeable in:
Indices: -
- Ready to switch on
Type: O2
- Operation enabled
index1: 3
Menus:
Min: 0
- Parameter menu
Max: 3
- Upread/free access
Unit: -
Changeable in:
Indices: 30
- Ready to switch on
Type: O2
- Operation enabled
110