Parameter
Description
P117
Corner points for describing the linear adaption of the gain
Kp-Adapt.
factor Kp of the current controller as a function of the
curve of the inductivity of the synchronous machine.
117
Index 1: Value of current at which the linear reduction
begins (up to which the inductivity has the value of P120.1)
Index 2: Value of current at which the linear reduction
ends (from which the inductivity has the value of P120.2)
P119*
Function parameter for entering the ratio of
Ratio Lq/Ld
the mutual inductance transversal to the rotor-axis (Lq)
to the mutual inductance along the rotor-axis (Ld)
119
of a connected synchronous motor.
The parameter value is calculated during the automatic
motor data identification of derived motor data (P115).
P120*
Function parameter for entering the main field inductance
Main Field Induc
(in mH) of a connected synchronous motor. The value to
be entered is 1.5 times the inductance of a winding phase
120
in the star equivalent circuit.
P121*
Function parameter for entering the stator resistance of a
Stator Resist
connected synchronous or induction motor. The value to
be entered corresponds to the ohmic resistance of a
121
winding phase at 20°C.
P122*
Function parameter for entering the total leakage
Tot Leak React
reactance of a connected induction motor. The value to be
entered corresponds to the total leakage reactance of a
122
winding phase. The parameter value is calculated during
the automatic calculation of derived motor data (P115).
P123*
Function parameter for entering the stator reactance of a
Stator React
connected induction motor. The value to be entered
corresponds to the stator reactance of a winding phase at
123
40% of the rated motor current. The parameter value is
calculated during the automatic calculation of derived
motor data (P115).
P124*
Function parameter for entering the rotor time constant of
Rotor TimeConst
a connected induction motor. The parameter value is
calculated during the automatic calculation of derived
124
motor data (P115).
Siemens AG
6SE7087-6QX70 (Edition AG)
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
index1: 0,00
Menus:
Min: 0,00
- Parameter menu
Max: 1300,00
+ Motor/encoder
Unit: A
+ Motor data
Indices: 2
- Drive setting
Type: I4
- Upread/free access
Changeable in:
- Drive setting
Init: 0,880
Menus:
Min: 0,200
- Parameter menu
Max: 5,000
+ Motor/encoder
Unit: -
+ Motor data
Indices: -
- Drive setting
Type: O2
- Upread/free access
Changeable in:
- Drive setting
index1: 0,000
Menus:
Min: 0,000
- Parameter menu
Max:
+ Motor/encoder
2000,000
+ Motor data
Unit: -
- Drive setting
Indices: 2
- Upread/free access
Type: O4
Changeable in:
- Drive setting
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 50000
+ Motor/encoder
Unit: mOhm
+ Motor data
Indices: 2
- Drive setting
Type: O2
- Upread/free access
Changeable in:
- Drive setting
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 65535
+ Motor/encoder
Unit: mOhm
+ Motor data
Indices: 2
- Drive setting
Type: O2
- Upread/free access
Changeable in:
- Drive setting
Init: 0,00
Menus:
Min: 0,00
- Parameter menu
Max: 655,00
+ Motor/encoder
Unit: Ohm
+ Motor data
Indices: -
- Drive setting
Type: O2
- Upread/free access
Changeable in:
- Drive setting
Init: 0
Menus:
Min: 0
- Parameter menu
Max: 10000
+ Motor/encoder
Unit: ms
+ Motor data
Indices: -
- Drive setting
Type: O2
- Upread/free access
Changeable in:
- Drive setting
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents