Advertisement

Parameter
Description
P703*
Function parameter for entering the number of PcDs for
SCom PcD #
the serial interfaces with USS protocol. The number of
PcDs defines the number of words in the telegram which
703
are to be used for transmitting control words and setpoints
or status words and actual values.
Index 1: Serial interface 1 (SCom1)
Index 2: Serial interface 2 (SCom2)
Index 3: SCB
The settings in indices 2 and 3 have no significance for
Compact PLUS units.
In the case of a factory setting via SCom1, SCom2 or
SCB2, this parameter is not reset.
P704*
Function parameter for entering the telegram failure time
SCom TlgOFF
for the serial interfaces with USS protocol.The telegram
failure time defines the time within which a valid telegram
704
has to be received. If no valid telegram is received within
the specified time, the unit trips a fault. With the help of
P781, tripping of the fault can be delayed and the drive
shut down if necessary. If a parameter value of 0 is
entered, there is no monitoring. This setting is to be
selected for non-cyclical telegram transmission (e.g. for
OP1S).
Index 1: Serial interface 1 (SCom(/SCom1)
Index 2: Serial interface 2 (SCom2)
Index 3: SCB
The settings in indices 2 and 3 have no significance for
Compact PLUS units.
In the case of a factory setting via SCom1, SCom2 or
SCB2, this parameter is not reset.
P705*
Direct transfer of peer-to-peer receive data of the SCB
SCB Peer2PeerExt
Identification of the words of the received peer-to-peer
telegram which are to be transferred directly.
705
Parameter values: 0: no direct transfer (only to CU)
not Compact PLUS
Indices: i001 = Word1 in PZD part of the telegram
Precondition: P696 = 3 (Peer-to-Peer protocol)
P706*
BICO parameter for selecting the connectors which are to
S.SCB TrnsData
be transmitted from the serial interface on the SCB. In
addition to the connectors themselves, their place in the
706
transmit telegram will also be defined.
not Compact PLUS
Index 1: Word 1 in PZD part of the telegram
Index 2: Word 2 in PZD part of the telegram
...
Index 16: Word 16 in PZD part of the telegram
The word 1 should be assigned with the status word 1
(K0032).
With double-word connectors, the relevant connector
number must be entered at 2 consecutive indices, as
otherwise only the higher-value word will be transferred.
The number of the words transferred in the PZD part of
the telegram is set in P703, Index i003.
IMPORTANT: With P696 = 3 (Peer-to- peer protocol) a
maximum of 5 words can be transferred (i001 to i005).
Siemens AG
6SE7087-6QX70 (Edition AG)
SIMOVERT MASTERDRIVES Compendium Motion Control
1: direct transfer (and transfer to CU)
i002 = Word2 in PZ part of the telegram
...
i005 = Word5 in PZD part of the telegram.
Data
Read/write
index1: 2
Menus:
Min: 0
- Parameter menu
Max: 16
+ Communication
Unit: -
+ SCom1/SCom2
Indices: 3
+ SCB/SCI
Type: O2
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 6500
+ Communication
Unit: ms
+ SCom1/SCom2
Indices: 3
+ SCB/SCI
Type: O2
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 1
+ Communication
Unit: -
+ SCB/SCI
Indices: 5
- Upread/free access
Changeable in:
Type: O2
- Ready to switch on
- Operation enabled
index1: 0
Menus:
Unit: -
- Parameter menu
Indices: 16
+ Communication
Type: L2 ,K
+ SCB/SCI
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
90