Conf MOP
0000 ... 0111
P425 (0110)
MOP storage:
Ramp generator MOP:
Initial rounding MOP:
Raise MOP from control
word 1 bit 13 [180.7]
Lower MOP from control
word 1 bit 14 [180.7]
0 0
MOP (max)
0 1
-200.0 ... 200.0 %
P421.F (100.0)
MOP (min)
1 0
-200.0 ... 200.0 %
P422.F (0.0)
1 1
1
2
Setpoint channel
Motorized potentiometer
0 Mot. potentiometer setpoint is not stored.
Starting point is specified after ON by P426 StartValue MOP.
1 Mot. potentiometer setpoint is stored in a non-volatile manner after OFF.
After ON, the mot. potentiometer is set to this value.
0 Ramp generator is not active in automatic mode.
Accel./decel. time =0
1 Ramp generator is always active
0 Without initial rounding
1 With initial rounding (the times set in P431 and P432 are
therefore not precise. P431 and P432 relate to a setpoint of 100 %).
Src MOP inv.
Src Manual/Auto
P423 (0)
P430 (0)
B
B
0
0
-1
1
1
Src Auto Setp
P429 (0)
KK
0
-1
1
3
4
<1>
MOP Accel Time
0.0 ... 1000.0 s
P431.F (10.0)
MOP (Input)
KK0057
MOP
(Implementation via internal
ramp generator with fixed
initial rounding)
Src SetV MOP
P428 (0)
KK
Src Set MOP
P427 (0)
B
ON from sequence control [180.7]
5
V2.4
fp_mc_300_e.vsd
18.01.06
<1>
For U953.71 = 10, P431 = 0.1 ms or
P432 = 0.1 ms is not permissible.
<1>
MOP Decel Time
0.0 ... 1000.0 s
P432.F (10.0)
P426.F (0.0)
-200 ... 200.0 %
StartValue MOP
6
7
Function diagram
MASTERDRIVES MC
U953.71 = 3
MOP (Out)
r424
MOP (Output)
KK0058
8
- 300 -