On position 1
Off position 1
Value range of
On/Off positions:
-2 147 483 647..
2 147 483 647
On position 2
Off position 2
1
2
Free blocks
Cam-contactor groups
1 extended cam-contactor group with 2 cams
U950.80 = __ (20)
U437
.01
U436
Cam3 FSetp1
KK (0)
.02(0)
.02
KK0566
KK (566)
.03(0)
.03
KK0567
KK (567)
Cam3 FSetp2
U436
Cam3 FSetp3
U437
.04(0)
.04
KK0568
KK (568)
.05(0)
.05
KK0569
KK (569)
Cam3 FSetp4
<1> If the input variable is a rotary axis and a cam passes the axis cycle jump of the
rotary axis, the axis cycle of the rotary axis has to be entered in parameter U436.6.
To ensure that cam 1 does not overlap with itself, the following restriction must be
observed:
The hysteresis must be smaller than half the difference between the axis cycle and
the cam size. If this condition is not fulfilled, the output binector remains off.
3
4
Hysteresis
0..2 147 483 647
ON position 1
U436.01 (0)
OFF position 1
Y1
Hyst
Hyst
Y2
Hyst
Hyst
ON position 2
OFF position 2
U436.6 (0)
Axis cycle
0..2 147 483 647
5
6
V2.4
fp_mc_745a_e.vsd
12.08.04
Y1
B0484
X
<1>
Y2
B0485
X
7
8
Function diagram
- 745a -
MASTERDRIVES MC