Parameter
Description
r967
Visualization parameter for displaying control word 1. Bits
Control Word 1
0 to 15 are displayed.
967
r968
Visualization parameter for displaying status word 1. Bits
Status Word 1
0 to 15 are displayed.
968
P970*
Function parameter for starting the parameter reset to a
Factory Setting
factory or fixed setting. After completion of the factory
setting, this parameter is also reset to its original value, 1.
970
0 = Start parameter reset
1 = No parameter reset
Caution: A parameter reset causes the loss of all
parameter changes.
If the factory setting of the parameter is made via an
interface (SCom1, SCom2, SCB2, 1st CB, 2nd CB) to 0 =
"Start parameter reset", the following parameters are not
reset:
SCom1, SCom2: P053, P700-704
SCB2: P053, P700-704, P696
1st CB, 2nd CB: P053, P711-722, P918
The following parameters are only reset to a certain extent:
P050, P072
P971*
Function parameter for starting saving of the parameters
EEPROM Saving
from the RAM to the EEPROM. Volatilely stored
parameters can be transferred to the EEPROM by
971
overwriting a parameter value of 0 with 1. The parameter
values are then stored non-volatilely and are secured
against mains failure.
0 = No saving
1 = One-time saving
The parameter must be reset manually to 0.
P972*
Power-On reset
Power On Reset
The Power-On reset works in the same way as Electronic
972
voltage Off -> On. This initializes the control board and
leads to a loss of communication. This value should
therefore not normally be included in a download file.
r979
Reserved for future use (currently not implemented)
Encoder Format
Profibus-specific parameter
979
This parameter describes the encoder characteristics
according to PROFIdrive V3.1.
r980
Visualization parameter for displaying the first 100
Par # List pt1
parameter numbers in the range 0 to 999. The parameter
numbers are arranged in ascending order. The first 0
980
occuring in the index signals that there are no further
parameter numbers. If the number of indices is not
sufficient to display all parameter numbers, index 101
contains the parameter numbers in which the list is
continued.
Siemens AG
6SE7087-6QX70 (Edition AG)
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: -
- Upread/free access
Type: V2
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: -
- Upread/free access
Type: V2
Init: 1
Menus:
Min: 0
- Parameter menu
Max: 1
+ Functions
Unit: -
- Fixed settings
Indices: -
- Upread/free access
Type: O2
Changeable in:
- Board configuration
- Drive setting
- Ready to switch on
Init: 0
Menus:
Min: 0
- Parameter menu
Max: 1
+ General parameters
Unit: -
- Upread/free access
Indices: -
Changeable in:
Type: O2
- Ready to switch on
- Operation enabled
Init: 0
Menus:
Min: 0
- Parameter menu
Max: 1
- Board configuration
Unit: -
- Drive setting
Indices: -
- Upread/free access
Type: O2
- Power section definition
Changeable in:
- Power section definition
- Board configuration
- Drive setting
- Ready to switch on
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 31
- Upread/free access
Type: O4
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 101
- Upread/free access
Type: O2