Communication / CBC
8.4-42
P719 (CB parameter 9)
CAN identifier for PKW-task broadcast
With this parameter, the CAN identifier for PKW-task broadcast (parameter
task) can be set. A broadcast telegram is to be received by all slaves on the
bus. This parameter must therefore be set the same for all slaves. With the
help of this function, a parameter task can be simultaneously issued to all
slaves on the bus.
The parameter reply is given with the CAN identifier of the PKW-reply (see
P711 / P696), namely
(Parameter value of P711 / P696) + (Parameter value of P918)*2 + 1
With the value 0 (pre-assigned) in this parameter, PKW-task broadcast is
deactivated.
If the calculated CAN identifier for PKW-task broadcast is outside the valid
range (1 to 2000) or if it overlaps another CAN identifier, error F080 appears
when status 4 "hardware configuration" is left. After acknowledgements of the
error, you are in the "hardware configuration" status again and can correct the
incorrect parameterization.
Example:
The basic identifier for parameterization in P711 / P696 is set to 1500. The
node address in P918 is 50. This results in a CAN identifier of 1500 + 50*2 =
1600 for PKW-task and 1601 for PKW-reply. The CAN identifier for PKW-
reply broadcast in P719 / P704 is set to 1900. A parameter task can be
issued by means of PKW-task broadcast, namely with CAN identifier 1900,
whereas the reply is given with CAN identifier 1601 by means of PKW-reply.
P720 (CB parameter 10)
Baud rate of the slave on the CAN bus
With this parameter, the baud rate of the slave on the CAN bus is set. The
following applies:
If the baud rate is outside the valid range, error F080 appears when status 4
"hardware configuration" is left. After acknowledgement of the error, you are
in the "hardware configuration" status again and can correct the incorrect
parameterization.
0
Parameter value
10
Baud rate [kBit/s]
Compendium Motion Control
P704 (CB parameter 9)
P705 (CB parameter 10)
1
2
3
4
20
50
100
125
6SE7087-6QX70 (Version AD)
SIMOVERT MASTERDRIVES
10.2004
5
6
7
8
250
500
800
1000
Siemens AG