Siemens SIMOVERT MASTERDRIVES Manual page 442

Motion control
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

Communication / SIMOLINK
8.3.6
Diagnostics of the peer-to-peer functionality
LED displays
Operating display
Fault display
Binectors
NOTE
8.3-14
The following diagnostics information is available to the user:
Three LED displays are provided on the front section of the SLB
optional board which supply information on the current operating status.
LED
Status
Green
Flashing Fault-free net data transfer via SIMOLINK
Red
Flashing SLB operating
Yellow
Flashing Data exchange with basic unit is okay
Table 8.3-1
SLB operating display
LED
Status
Green
off/on
No net data exchange possible via SIMOLINK;
bus cable is not connected or is defective
Red
off/on
Voltage supply for SLB cut off;
replace SLB or basic unit
Yellow
off/on
No data exchange with the basic unit;
bus cable is not connected or is defective;
replace SLB or basic unit
Table 8.3-2
SLB fault display
♦ B0041: Time out:
Bit = 1 indicates that an interruption has occurred in cyclic data
transfer. This status remains active until cyclic data transfer has
been resumed.
The reaction time is permanently stored in the SLB and cannot be
changed.
Every time "Time out" occurs, the SLB diagnostics parameter (r748,
Index 3) is incremented by the value 1 (→ statistics).
At the same time, the address of the node that has first noticed the
interruption in the ring can be upread in r748, Index 5.
♦ B0040: SLB telegram failure
Bit = 1 indicates that the telegram failure time set in the "SLB
TlgOFF" parameter (P741) has run out in this node, without a valid
SYNC signal having been received.
♦ B0042: Start alarm
Bit = 1 indicates that the SIMOLINK ring is physically open and that
a start cannot be carried out. This status is also signaled by alarm
A002.
Bit = 0 indicates that the SIMOLINK ring is physically closed.
♦ B0043: Drive synchr. (only MC)
Bit = 1 indicates whether the CU is synchronized to the SIMOLINK
BUS. Corresponds to the inverse of alarm A003.