Delta ASDA-B2 Series User Manual page 230

Standard ac servo drive for general purpose applications
Table of Contents

Advertisement

ASDA-B2
P2-47
ANCF
Operation
Interface:
Default: 1
Control
Mode:
Range: 0 ~ 2
Data Size: 16-bit
Format: Decimal
Settings: 0: The value of P2-43, P2-44 and P2-45, P2-46 will retain.
P2-48
ANCL Resonance Suppression Detection Level
Operation
Interface:
Default: 100
Control
Mode:
Range: 1 ~ 300%
Data Size: 16-bit
Format: Decimal
Settings: (The smaller the setting value is, the more sensitive the
Revision May, 2018
Auto Resonance Suppression Mode
Setting
Panel/Software
ALL
Unit: N/A
1: The value of P2-43, P2-44 and P2-45, P2-46 will retain after
resonance suppression.
2: Continuous resonance suppression
Description of Auto Mode Setting:
When it is set to 1: Auto resonance, the value returns to 0
automatically and saves the point of resonance suppression
when it is stable. If it is unstable, re-power on or set back to 1 for
re-estimation again.
When it is set to 2: Continuous suppression automatically. When
it is stable, the point of resonance suppression will be saved. If it
is unstable, re-power on for re-estimation.
When switching to mode 0 from mode 2 or 1, the setting of P2-43,
P2-44, P2-45, and P2-46 will be saved automatically.
Panel/Software
ALL
Unit: N/A
resonance will be.)
The setting value of P2-48 ↑, resonance sensitivieness ↓.
The setting value of P2-48 ↓, resonance sensitivieness ↑.
Communication
Communication
Chapter 7 Parameters
Address: 025EH
025FH
Related Section: N/A
Address: 0260H
0261H
Related Section: N/A
7-69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents