Chapter 7 Parameters
P1-56
OVW Output Overload Warning Level
Operation
Interface:
Default: 120
Control
Mode:
Range: 0 ~ 120
Data Size: 16-bit
Format: Decimal
Settings: The setting value is 0 ~ 100, if the servo motor continuously
P1-57
CRSHA
Operation
Interface:
Default: 0
Control
Mode:
Range: 0 ~ 300
Data Size: 16-bit
Format: Decimal
Settings: Setup protection level (for the percentage of rated torque, set the
P1-58
CRSHT Motor Crash Protection Time
Operation
Interface:
Default: 1
Control
Mode:
Range: 0 ~ 1000
Data Size: 16-bit
Format: Decimal
Settings: Setup the protection time:
7-46
Panel/Software
ALL
Unit: %
outputs the load and is higher than the setting proportion (P1-56),
the early warning for overload (DO is set to 10, OLW) will occur.
If the setting value is over 100, it will disable this function.
Motor Crash Protection (Torque
Percentage)
Panel/Software
ALL
Unit: %
value to 0 means to disable the function, set the value to 1 or
number above means to enable the function).
Panel/Software
ALL
Unit: ms
When it reaches the level, AL.030 occurs after exceeding the
protection time.
Communication
Communication
Communication
ASDA-B2
Address: 0170H
0171H
Related Section: N/A
Address: 0172H
0173H
Related Section: N/A
Address: 0174H
0175H
Related Section: N/A