Goodrive350 series high-performance multifunction VFD
Function
Name
code
P00.17
Reserved
Function
P00.18
parameter
restoration
P01––Start/stop control
Function
Name
code
Running mode of
P01.00
start
Starting
P01.01
frequency of
direct start
Hold time of
P01.02
starting
frequency
Description
eliminate the impact on the output voltage of VFD
when bus voltage fluctuates.
0: No operation
1: Restore default values (excluding motor
parameters)
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test mode)
6: Restore default values (including motor
parameters)
Note: After the selected operation is performed,
this parameter is automatically restored to 0.
Restoring the default values may delete the user
password. Exercise caution when using this
function. The option 5 can be used only for factory
testing.
Description
0: Direct start
1: Start after DC brake
2: Start after speed tracking
Starting frequency of direct startup is the initial
frequency when the VFD starts. See P01.02 (hold
time of starting frequency) for details.
Setting range: 0.00–50.00Hz
Output frequency
fmax
f1 set by P01.01
t1 set by P01.02
f1
t1
A proper starting frequency can increase the
torque during startup. Within the hold time of
starting frequency, the output frequency of VFD is
the starting frequency, and then it runs from the
starting frequency to the target frequency, if the
target frequency (frequency command) is below
-141-
Function parameter list
t
Default
Modify
value
◎
0
Default
Modify
value
◎
0
◎
0.50Hz
◎
0.0s
Need help?
Do you have a question about the Goodrive350 Series and is the answer not in the manual?