Goodrive350 series high-performance multifunction VFD
Function
Name
code
Initial pole
P13.01
detection mode
P13.02
Pull-in current 1
P13.03
Pull-in current 2
Pull-in current
P13.04
switchover
frequency
High-frequency
superposition
P13.05
frequency
(reserved)
Pulse current
P13.06
setting
P13.07
Reserved
Control
P13.08
parameter 1
Frequency
P13.09
threshold of
Description
current)
0: No detection
1: High-frequency current injection
2: Pulse superimposition
Pull-in current is the pole position orientation
current; pull-in current 1 is valid within the lower
limit of pull-in current switchover frequency
threshold. If you need to increase the starting
torque, increase the value of this function code
properly.
Setting range: 0.0%–100.0% (of the motor rated
current)
Pull-in current is the pole position orientation
current; pull-in current 2 is valid within the upper
limit of pull-in current switchover frequency
threshold, and you do not need to change pull-in
current 2 under common situations.
Setting range: 0.0%–100.0% (of the motor rated
current)
0.0%–200.0% (of the motor rated current)
/
This parameter is used to set the pulse current
threshold when the initial magnetic pole position is
detected in the pulse mode. The value is a
percentage in relative to the rated current of the
motor.
Setting range: 0.0–300.0% (of the motor rated
voltage)
/
0x0000–0xFFFF
This parameter is used to set the frequency
threshold for enabling the counter-electromotive
-213-
Function parameter list
Default
Modify
value
◎
0
○
20.0%
○
10.0%
○
20.0%
/
/
◎
100.0%
/
/
○
0x0000
○
50.00