Goodrive350 series high-performance multifunction VFD
Function
Name
code
Corresponding
P25.30
setting of lower
limit of AI4
Upper limit value
P25.31
of AI4
Corresponding
P25.32
setting of upper
limit of AI4
Input filter time of
P25.33
AI4
HDI3 high-speed
P25.34
pulse input
function
Lower limit
P25.35
frequency of
HDI3
Corresponding
setting of lower
P25.36
limit frequency of
HDI3
Upper limit
P25.37
frequency of
HDI3
Description
100%
Input filter time: Adjust the sensitivity of analog
input, increase this value properly can enhance
the anti-interference capacity of analog variables;
however, it will also degrade the sensitivity of
analog input.
Note: AI3 and AI4 can support 0–10V/0–20mA
input, when AI3 and AI4 select 0–20mA input, the
corresponding voltage of 20mA is 10V.
Setting range of P25.24: 0.00V–P25.26
Setting range of P25.25: -300.0%–300.0%
Setting range of P25.26: P25.24–10.00V
Setting range of P25.27: -300.0%–300.0%
Setting range of P25.28: 0.000s–10.000s
Setting range of P25.29: 0.00V–P25.31
Setting range of P25.30: -300.0%–300.0%
Setting range of P25.31: P25.29–10.00V
Setting range of P25.32: -300.0%–300.0%
Setting range of P25.33: 0.000s–10.000s
0: Set input via frequency
1: Count
0.000 kHz – P25.37
-300.0%–300.0%
P25.35 –50.000kHz
-258-
Corresponding
setting
AI
0
10V
20mA
AI3/AI4
-100%
Function parameter list
Default
Modify
value
0.0%
10.00V
100.0%
0.030s
0
0.000
kHz
0.0%
50.000
kHz