Goodrive350 series high-performance multifunction VFD
16:02:35
Fwd
P17.00:Set Freq
P17.11:DC Bus Volt
P17.12:HDIB/A/S4/3/2/1
P17.13:RO2/RO1/HDO/Y1
P17.26:Current Oper Time
P17.15:Motor Trq Ref
Back
5.4.8 Autotuning motor parameters
You can choose Menu > Motor parameter autotune and press
enter motor parameter autotuning interface. However, before entering the motor parameter
autotuning interface, you must set the motor nameplate parameters correctly. After entering the
interface, select a motor autotuning type to carry out motor parameter autotuning. In motor parameter
autotuning interface, you can press
16:02:35
Fwd
Local
Ready
Parameter groups
User defined parameters
State monitoring
Motor parameter autotune
Copy parameter/Restore default
System settings
Back
Home
After selecting a motor autotuning type, enter motor parameter autotuning interface, and press RUN
key to start motor parameter autotuning. After autotuning is done, a message will pop up indicating
autotuning is succeeded, and then it will return to the main interface of stop. During autotuning, you
can press STOP/RST key to terminate autotuning; if any fault occur during autotuning, the keypad will
display a fault interface.
16:02:35
Autotune steps:0
Autotuning parameters...
5.4.9 Backing up parameters
You can choose Menu > Copy parameter/Restore default, and press
key to enter the function parameter backup interface and function parameter restoration interface to
upload/download VFD parameters, or restore VFD parameters to default values. The keypad has
three different storage areas for parameter backup, and each storage area can save the parameters
of one VFD, which means the keyapd can save parameters of three VFDs in total.
Local
Ready
GD350
Add
OK
Figure 5-17 State monitoring interface
GD350
16:02:35
Ensure motor nameplate parameters are set
correctly.
Sele
Back
Figure 5-18 Selecting a parameter autotuning type
Fwd
Local
Run
GD350
Back
Home
Figure 5-19 Parameter autotuning
16:02:35
Set Freq
Max
Min
Default
Back
key or
key to return to the previous menu.
Fwd
Local
Ready
GD350
Home
OK
16:02:35
Fwd
Autotune steps:3
Parameters autotuned
...
OK
Back
-48-
Basic operation guidelines
Fwd
Local
Ready
GD350
Hz
50.00
: 630.00
: 0.0
: 0.0
Home
OK
key,
key or
16:02:35
Fwd
Complete para rotary autotune
Complete para static autotune
Partial para static autotune
Complete para rotary autotune 2 (for AM)
Partial para static autotune 2 (for AM)
Back
Local
Run
GD350
Home
OK
key,
key to
Local
Ready
GD350
Home
OK
key or
Need help?
Do you have a question about the Goodrive350 Series and is the answer not in the manual?
Questions and answers