Goodrive350 series high-performance multifunction VFD
Fault
Fault type
code
[61] Failed to identify
F2-Er
the expansion card
in card slot 2
[62] Failed to identify
F3-Er
the expansion card
in card slot 3
[63] Communication
timeout occurred to
C1-Er
the expansion card
in card slot 1
[64] Communication
C2-Er
timeout occurred to
Possible cause
There is data transmission in
interfaces of card slot 2,
however, it cannot read the
card type
There is data transmission in
interfaces of card slot 3,
however, it cannot read the
card type
There is no data
transmission in interfaces of
card slot 1
There is no data
transmission in interfaces of
-286-
Troubleshooting
Corrective measures
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
Confirm whether the expansion
card inserted can be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
Confirm whether the expansion
card inserted can be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
Confirm whether the expansion
card inserted can be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes, replace
the insertion port after power
down
Confirm whether the expansion
card inserted can be supported;