Goodrive350 series high-performance multifunction VFD
Function
Name
code
P28.03 Slave speed gain 0.0–500.0%
P28.04 Slave torque gain 0.0–500.0%
Speed/torque
mode switching
P28.05
frequency point
in master/slave
mode 2
P28.06
Slave count
P28.07–
Reserved
P28.08
CAN slave torque
P28.09
offset
Enabling EC
PT100/PT1000 to
P28.10
detect
temperature
EC PT100
detected OH
P28.11
protection
threshold
EC PT100
detected OH
P28.12
pre-alarm
threshold
EC PT100
detected
temperature
P28.13
calibration upper
limit
Description
Tens place: Slave start command source selection
0: Follow the master to start
1: Determined by P00.01
Hundreds place: Slave transmitting/master
receiving data enable
0: Enable
1: Disable
0.00–10.00Hz
1–15
/
-100.0–100.0%
0x00–0x11
Ones place: PT100 temperature detection
0: Disable
1: Enable
Tens place: PT1000 temperature detection
0: Disable
1: Enable
Protection threshold of overheating (OH) detected
by the expansion card (EC) with PT100.
0.0–150.0° C
Pre-alarm threshold of OH detected by the EC with
PT100.
0.0–150.0° C
Calibration upper limit of temperature detected by
the EC with PT100.
50.0–150.0° C
-266-
Function parameter list
Default Modify
○
100.0%
○
100.0%
○
5.00Hz
◎
1
/
/
○
0.0%
◎
0x00
○
120.0° C
○
100.0° C
○
120.0° C