P01--Start/Stop Control - INVT Goodrive350 Series Operation Manual

High-performance multifunction vfd
Hide thumbs Also See for Goodrive350 Series:
Table of Contents

Advertisement

Goodrive350 series high-performance multifunction VFD
Function
Name
code
P00.17
Reserved
Function
P00.18
parameter
restoration
P01––Start/stop control
Function
Name
code
Running mode of
P01.00
start
Starting
P01.01
frequency of
direct start
Hold time of
P01.02
starting
frequency
DC brake current
P01.03
before start
Description
Reserved
0: No operation
1: Restore to default value
2: Clear fault history
Note: After the selected function operations are
done, this function code will be restored to 0
automatically. Restoration to default value will
clear the user password, this function should be
used with caution.
Description
0: Direct start
1: Start after DC brake
2: Start after speed-tracking 1
3: Start after speed-tracking 2
Starting frequency of direct startup is the initial
frequency when the VFD starts. See P01.02 (hold
time of starting frequency) for details.
Setting range: 0.00–50.00Hz
Output frequency
fmax
f1
t1
A proper starting frequency can increase the
torque during startup. Within the hold time of
starting frequency, the output frequency of VFD is
the starting frequency, and then it runs from the
starting frequency to the target frequency, if the
target frequency (frequency command) is below
the starting frequency, the VFD will be standby
rather than running. The starting frequency value
is unlimited by the lower limit frequency.
Setting range: 0.0–50.0s
During starting, the VFD will first perform DC brake
based on the set DC brake current before startup,
-132-
F1 set by P01.01
T1 set by P01.02
T
Function parameter list
Default
Modify
value
0
Default
Modify
value
0
0.50Hz
0.0s
0.0%