Delta VFD300C43S-HS User Manual page 466

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
 Group setting 10: Air Handling Unit, AHU
The following table lists the relevant AHU setting application parameters.
Pr.
00-04
Content of multi-function display
00-11
Speed control mode
00-16
Load Selection
Master frequency command source (AUTO)
00-20
/ Source selection of the PID target
00-21
Operation command source (AUTO)
00-22
Stop method
00-23
Control of motor direction
00-30
Master frequency command (HAND) source
00-31
Operation Command (HAND) source
01-00
Maximum operation frequency
01-01
Output frequency of motor 1
01-02
Output voltage of motor 1
01-07
Minimum output frequency of motor 1
01-10
Output frequency upper limit
01-11
Output frequency lower limit
01-34
Zero-speed mode
01-43
V/F curve selection
02-05
Multi-function input command 5 (MI5)
02-13
Multi-function output 1 RLY1
02-14
Multi-function output 2 RLY2
03-00
Analog input selection (AVI)
03-01
Analog input selection (ACI)
03-02
Analog input selection (AUI)
03-28
AVI terminal input selection
03-29
ACI terminal input selection
03-20
Multi-function output 1 (AFM1)
03-23
Multi-function output 2 (AFM2)
03-31
AFM2 output selection
03-50
Analog input curve selection
07-06
Restart after momentary power loss
07-11
Number of times of restart after fault
07-33
Auto-restart interval of fault
 
Explanation
12.1-13-4
Settings
2
0 (V/F control)
0 (Normal load)
2 or 0
1 or 0
1 (Coast to stop)
1 (Disable reverse)
0 (Digital keypad)
0 (Digital keypad)
50
50
380
0.1
50
35
2
2
16 or 17
11
1
1
1
1
0
1
0
0
0 or 1
4 (three-point curve of AUI)
2 (Speed tracking by minimum output
frequency)
5 (times)
60 (s)