Delta VFD300C43S-HS User Manual page 475

Vector control drive (high speed models)
Table of Contents

Advertisement

Output Frequency of Motor 1 (Base Frequency and Motor Rated Frequency)
Settings
The upper limit is the same as the maximum operation frequency of Pr.01-00.
Set this value according to the motor's rated frequency from the motor's nameplate. If the
motor's rated frequency is 600Hz, set the value to 600Hz. If the motor's rated frequency is
500Hz, set the value to 500Hz.
Output Voltage of Motor 1 (Base Frequency and Motor Rated Frequency)
Settings
Set this value according to the motor's rated voltage from the motor's nameplate. If the motor's
rated voltage is 440V, set the value to 440.0V. If the motor's rated voltage is 400V, set the value
to 400.0V.
There is a wide variety of motors, but the power system for each country is difference. The
convenient and economical way to solve this problem is to use an AC motor drive, which can
deal with different voltages and frequencies, while supporting the original characteristic and life
of the motor.
Motor Parameter Auto-tuning
Settings
Rated Power for Induction Motor 1 (kW)
Settings
Sets the rated power for motor 1. The default is the drive's power value.
Rated Speed for Induction Motor 1 (rpm)
Settings
 Sets the rated speed for the motor as indicated on the motor nameplate.
5: IMFOC Sensorless (IM FOC sensorless)
6: PM Sensorless (PM FOC sensorless)
7: IPM Sensorless (Interior PM FOC sensorless)
0.0–1500.0Hz
0.0–510.0V
0: No function
1: Simple rolling auto-tuning for induction motor (IM)
2: Static auto-tuning for induction motor (IM)
4: Dynamic test for PM magnetic pole (with the running in forward direction)
5: Rolling auto-tuning for PM
6: Advanced rolling auto-tuning for IM flux curve
12: FOC Sensorless inertia estimation
13: Static auto-tuning for PM
0.00–655.35 kW
0
xxxx (Depending on the motor pole number)
12.2-00-5
Chapter 12 Description of Parameter SettingsC2000-HS
Default: 600.
Default: 400.0
Default: 0
Default: Depending
on the model power
Default: Depending on
the motor pole number

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents