Delta VFD300C43S-HS User Manual page 381

Vector control drive (high speed models)
Table of Contents

Advertisement

IGBT Temperature at Malfunction
Settings
 When a malfunction occurs, check the current IGBT temperature. If it happens again, it
overwrites the previous record.
Capacitance Temperature at Malfunction
Settings
 When a malfunction occurs, check the current capacitance temperature. If it happens again, it
overwrites the previous record.
Motor Speed in rpm at Malfunction
Settings
 When a malfunction occurs, check the current motor speed in rpm. If it happens again, it
overwrites the previous record.
Torque Command at Malfunction
Settings
 When a malfunction occurs, check the current torque command. If it happens again, it overwrites
the previous record.
Status of the Multi-function Input Terminal at Malfunction
Settings
Status of the Multi-function Output Terminal at Malfunction
Settings
 When a malfunction occurs, check the status of multi-function input / output terminals. If it
happens again, it overwrites the previous record.
Drive Status at Malfunction
Settings
 When a malfunction occurs, check the current drive status (communication address 2101H). If it
happens again, it overwrites the previous record.
STO Latch Selection
Settings
 Pr. 06-44 = 0: STO Alarm Latch. After you clear the cause of the STO Alarm, use a Reset
command to clear the STO Alarm.
-3276.7–3276.7ºC
-3276.7–3276.7ºC
-32767–32767 rpm
-32767–32767%
0000h–FFFFh
0000h–FFFFh
0000h–FFFFh
0: STO latch
1: STO no latch
12.1-06-15
Chapter 12 Description of Parameter SettingsC2000-HS
Default: Read only
Default: Read only
Default: Read only
Default: Read only
Default: Read only
Default: Read only
Default: Read only
Default: 0