Delta VFD300C43S-HS User Manual page 501

Vector control drive (high speed models)
Table of Contents

Advertisement

 No-load / Light-load Operation Adjustment
8. No-load running
(a) Set Pr.11-00 = 1 Auto-tuning for ASR and APR
(b) Start the motor without load, and operates the motor to 1/2 of rated rotor speed
a. If the start direction is wrong, starting rotation is not smooth (ocA) or the motor salient ratio
(Lq / Ld) is low, increase Pr.10-52 (Injection Magnitude) and Pr.10-42 (Initial Angle Detection
Pulse Value) to improve the accuracy of the angle detection.
b. If Pr.10-51 (Injection frequency) is close to the rated motor frequency (Pr.01-01), then
increase Pr.10-51 to avoid the angle detection difference caused by motor rated frequency.
9. Acceleration test with no-load / light-load
A1. Accelerate to rated frequency and observe if the motor operates stably.
a. If the motor output rotor speed presents periodic low-frequency wave, increase Pr.11-04
(ASR2 high-speed bandwidth), or increase Pr.10-32 (PM FOC sensorless speed
estimator bandwidth).
b. If the output frequency reflects high-frequency vibration, decrease Pr.11-04 or decrease
Pr.10-32.
A2. Accelerate the motor to the maximum frequency, and observe if it operates stably.
If the motor stalls when accelerating to the maximum rotor speed, increase Pr.10-32 (PM
FOC sensoress speed estimator bandwidth) and Pr.10-34 (PM sensorless speed
estimator low-pass filter gain).
※ Setting curve of speed regulator (ASR) and related parameters:
Parameter
Pr.11-00
Pr.11-01
Pr.11-02
Pr.11-03
Pr.11-04
Pr.11-05
Chapter 12 Description of Parameter SettingsC2000-HS
Description
System control
Per unit of system inertia
ASR1 / ASR2 switch frequency
(it is suggested to set the switch
frequency higher than Pr.10-39)
ASR1 low-speed bandwidth
ASR2 high-speed bandwidth
Zero-speed bandwidth
12.2-00-31
Default
0
256
7Hz
10Hz
10Hz
10Hz