Chapter 12 Description of Parameter SettingsC2000-HS
LOCAL / REMOTE Selection
Settings
The default for Pr. 00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and
operation source with Pr. 00-20 and Pr. 00-21. Set the HAND frequency and operation source
with Pr. 00-30 and Pr. 00-31. Select or switch AUTO / HAND mode by using the digital keypad
KPC-CC01 or setting the multi-function input terminal MIx = 41, 42.
When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr. 00-29 = 1,2,3,4
are disabled. The external terminal has the highest command priority, and Pr. 00-29 functions in
standard HOA mode.
When you do not set Pr. 00-29 to 0, the Local / Remote function is enabled, and the top right
corner of digital keypad KPC-CC01 (firmware version 1.021 and above) displays LOC or REM.
Set the LOCAL frequency and operation source with Pr. 00-20 and Pr. 00-21. Set the REMOTE
frequency and operation source with Pr. 00-30 and Pr. 00-31. Select or switch LOC / REM mode
with the digital keypad KPC-CC01 or set the multi-function input terminal MIx = 56. The AUTO
key of the digital keypad is for the REMOTE function, and HAND key is for the LOCAL function.
When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29
to 0, then the external terminal function is disabled.
When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not
set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command
priority.
Master Frequency Command (HAND) Source
Settings
Determines the master frequency source in HAND mode.
0: Standard HOA function
1: Switch Local / Remote, the drive stops
2: Switch Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switch Local / Remote, the drive runs as LOCAL setting when switched to
Local and runs as REMOTE setting when switched to Remote for
frequency and operation status.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal (multi-function input terminal)
4: Pulse input without direction command (Pr. 10-16 without direction)
5: Pulse input with direction command (Pr. 10-16)
6: CANopen communication card
8: Communication card (does not include CANopen card)
12.1-00-16
Default: 0
Default: 0