Delta VFD300C43S-HS User Manual page 282

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
LOCAL / REMOTE Selection
Settings
 The default for Pr. 00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and
operation source with Pr. 00-20 and Pr. 00-21. Set the HAND frequency and operation source
with Pr. 00-30 and Pr. 00-31. Select or switch AUTO / HAND mode by using the digital keypad
KPC-CC01 or setting the multi-function input terminal MIx = 41, 42.
 When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr. 00-29 = 1,2,3,4
are disabled. The external terminal has the highest command priority, and Pr. 00-29 functions in
standard HOA mode.
 When you do not set Pr. 00-29 to 0, the Local / Remote function is enabled, and the top right
corner of digital keypad KPC-CC01 (firmware version 1.021 and above) displays LOC or REM.
Set the LOCAL frequency and operation source with Pr. 00-20 and Pr. 00-21. Set the REMOTE
frequency and operation source with Pr. 00-30 and Pr. 00-31. Select or switch LOC / REM mode
with the digital keypad KPC-CC01 or set the multi-function input terminal MIx = 56. The AUTO
key of the digital keypad is for the REMOTE function, and HAND key is for the LOCAL function.
 When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29
to 0, then the external terminal function is disabled.
 When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not
set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command
priority.
Master Frequency Command (HAND) Source
Settings
 Determines the master frequency source in HAND mode.
0: Standard HOA function
1: Switch Local / Remote, the drive stops
2: Switch Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switch Local / Remote, the drive runs as LOCAL setting when switched to
Local and runs as REMOTE setting when switched to Remote for
frequency and operation status.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Refer to Pr. 03-00)
3: External UP / DOWN terminal (multi-function input terminal)
4: Pulse input without direction command (Pr. 10-16 without direction)
5: Pulse input with direction command (Pr. 10-16)
6: CANopen communication card
8: Communication card (does not include CANopen card)
12.1-00-16
Default: 0
Default: 0