Chapter 12 Description of Parameter SettingsC2000-HS
Motor Zero-speed Level
Settings
Use this parameter with the multi-function output terminals (set to 43). The motor needs to
install encoder to feedback the actual rotating speed and use with PG card or MI pulse input
terminal.
Use this parameter to set the level of motor at zero-speed. When the speed is lower than this
setting, the corresponding multi-function output terminal that is set to 43 is ON, as shown below:
Maximum Frequency of Resolution Switch
Settings
The upper limit of setting range is the same as the maximum operating frequency for Pr. 01-00.
Switch Delay Time of Maximum Output Frequency
Settings
Use to improve unstable speed or unstable position due to insufficient analog resolution. Use with
the external terminal (setting to 43). After setting this parameter, you also need to adjust the
analog output resolution of the controller to work with the parameter function.
0–65535 rpm
0.0–1500.0Hz
0.000–65.000 sec.
12.1-02-24
Default: 0
Default: 600.0
Default: 0.000