Chapter 11 Summary of Parameter SettingsC2000-HS
06 Protection Parameters
Pr.
Parameter Name
06-00
Low voltage level
06-01
Over-voltage stall prevention
Selection for over-voltage stall
 06-02
prevention
Over-current stall prevention
06-03
during acceleration
Over-current stall prevention
06-04
during operation
Acceleration / deceleration time
06-05
selection for stall prevention at
constant speed
Over-torque detection selection
06-06
(OT1)
06-07
Over-torque detection level (OT1)
06-08
Over-torque detection time (OT1)
Over-torque detection selection
06-09
(OT2)
06-10
Over-torque detection level (OT2)
06-11
Over-torque detection time (OT2)
 06-12
Current limit
Setting Range
Frame D0–D: 300.0–440.0V
Frame E and above: 380.0–440.0V
0: Disabled
0.0–900.0V
DC
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
0–160%
(100% corresponds to the rated current of the drive)
0–160%
(100% corresponds to the rated current of the drive)
0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
nd
2: By the 2
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time
th
4: By the 4
acceleration / deceleration time
5: By automatic acceleration / deceleration
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
10–250%
(100% corresponds to the rated current of the drive)
0.0–60.0 sec.
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after Over-torque detection during RUN
10–250%
(100% corresponds to the rated current of the drive)
0.0–60.0 sec.
0–170%
(100% corresponds to the rated current of the drive)
11-26
DC
DC
Default
360.0
400.0
760.0
0
120
120
0
0
120
0.1
0
120
0.1
170