Delta VFD300C43S-HS User Manual page 247

Vector control drive (high speed models)
Table of Contents

Advertisement

Pr.
Parameter Name
06-51
Capacitor oH warning level
06-52
Ripple of input phase loss
Detected input phase loss (OrP)
06-53
action
06-55
Derating protection
06-56
PT100 voltage level 1
06-57
PT100 voltage level 2
PT100 level 1 frequency
06-58
protection
PT100 activation level 1 protection
06-59
frequency delay time
Software detection GFF current
06-60
level
06-61
Software detection GFF filter time
06-62
dEb reset bias level
Operation time of fault record 1
06-63
(Day)
Operation time of fault record 1
06-64
(Min.)
Operation time of fault record 2
06-65
(Day)
Operation time of fault record 2
06-66
(Min.)
Operation time of fault record 3
06-67
(Day)
Operation time of fault record 3
06-68
(Min.)
Operation time of fault record 4
06-69
(Day)
Operation time of fault record 4
06-70
(Min.)
06-71
Low current setting level
06-72
Low current detection time
Chapter 11 Summary of Parameter SettingsC2000-HS
Setting Range
0.0–110.0 degree
0.0–320.0V
DC
0: Warn and ramp to stop
1: Warn and coast to stop
0: Constant rated current and limit carrier wave by
load current and temperature
1: Constant carrier frequency and limit load current by
setting carrier wave
2: Constant rated current (same as setting 0), but
close current limit
0.000–10.000 V
0.000–10.000 V
0.0–1500.0 Hz
0–6000 sec.
0.0–6553.5 %
0.00–655.35 sec.
0.0–200.0 V
DC
0–65535 days
0–1439 min.
0–65535 days
0–1439 min.
0–65535 days
0–1439 min.
0–65535 days
0–1439 min.
0.0–100.0 %
0.00–360.00 sec.
11-31
Default
Depending
on the
model
power
60.0
0
0
5.000
7.000
0.0
60
60.0
0.10
40.0
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
0.0
0.00