Chapter 16 PLC Function ApplicationsC2000-HS
H 0.00Hz
A 0.00Hz
C _ _ _ _ _
7.
In the PLC Run and PLC Stop mode, the content 9 and 10 of Pr. 00-02 cannot be set and cannot
be reset to the default value.
8.
The PLC can be reset to the default value when Pr. 00-02 is set as 6.
9.
The corresponding MI function will be disabled when the PLC writes to input contact X.
10. When the PLC controls converter operation, control commands will be entirely controlled by the
PLC and will not be affected by the setting of Pr. 00-21.
11. When the PLC controls converter frequency commands (FREQ commands), frequency
commands will be entirely controlled by the PLC, and will not be affected by the setting of Pr.
00-20 or the Hand ON/OFF configuration.
12. When the PLC controls converter frequency (TORQ commands), torque commands will be
entirely controlled by the PLC, and will not be affected by the setting of Pr. 11-33 or the Hand
ON/OFF configuration.
13. When the PLC controls converter frequency (POS commands), position commands will be
entirely controlled by the PLC, and will not be affected by the setting of Pr. 11-40 or the Hand
ON/OFF configuration.
14. When the PLC controls converter operation, if the keypad Stop setting is valid, this will trigger
an FStP error and cause stoppage.
Digital Keypad KPC-CC01
Can display 0–65535
16-4