Delta VFD300C43S-HS User Manual page 178

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 9 Specification C2000-HS
9-2 Environment for Operation, Storage and Transportation
DO NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive / inflammable gasses,
humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg / cm
Installation
location
Surrounding
Temperature
(°C)
Rated Humidity
Air Pressure
(kPa)
Environment
Pollution Level
Altitude
Storage
Package Drop
Transportation
1.0mm, peak to peak value range from 2Hz to 13.2 Hz; 0.7G–1.0G range from 13.2Hz to 55Hz; 1.0G range
Vibration
from 55Hz to 512Hz. Comply with IEC 60068-2-6
Impact
IEC / EN 60068-2-27
Maximum allowed offset angle 10
Operation
Position
installation position)
IEC60364-1 / IEC60664-1 Pollution degree 2, Indoor use only
Storage /
-25 – +70
Transportation
No condense water, non-frozen
Operation
Maximum 95%
Storage /
Maximum 95%
Transportation
No condense water
Operation /
86–106
Storage
Transportation
70–106
IEC 60721-3-3
Operation
Class 3C3; Class 3S2
Storage
Class 1C2; Class 1S2
Transportation
Class 2C2; Class 2S2
If you use the AC motor drive under harsh environment with high level of contamination
(e.g. dew, water, dust), make sure it is installed in an environment qualified for IP54 such as in
a cabinet.
If AC motor drive is installed at altitude 0–1000m, follow normal operation
restriction. If it is installed at altitude 1000–2000m, decrease 1% of rated
Operation
current or lower 0.5°C of temperature for every 100m increase in altitude.
Maximum altitude for Corner Grounded is 2000m.
ISTA procedure 1A (according to weight) IEC60068-2-31
o
(under normal
10
10
9-4
2
every year.
Table 9-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents