Command
Connect contact b in series
ANI
X0–X17
Operand
The ANI command is used to create a series connection to contact b; its function is to first read
current status of the designated series contact and logical operation results before contact in
order to perform "AND" operation; saves results in cumulative register.
Ladder diagram:
X1
Command
OR
Connect contact a in parallel
X0–X17
Operand
The OR command is used to establish a parallel connection to contact a; its function is to first
read current status of the designated series contact and logical operation results before
contact in order to perform "OR" operation; saves results in cumulative register.
Ladder diagram:
X0
X1
Command
ORI
Connect contact b in parallel
X0–X17
Operand
The ORI command is used to establish a parallel connection to contact a; its function is to first
read current status of the designated series contact and logical operation results before
contact in order to perform "OR" operation; saves results in cumulative register.
Ladder diagram:
X0
X1
Command
ANB
Series circuit block
Operand
ANB performs an "AND" operation on the previously saved logic results and the current
cumulative register content.
Ladder diagram:
X0
X2
Block A
Y0–Y17
M0–M799
X0
Y1
Y0–Y17
M0–M799
Y1
Y0–Y17
M0–M799
Y1
X1
ANB
Y1
X3
Block B
16-43
Chapter 16 PLC Function ApplicationsC2000-HS
Function
T0–159
Command code:
LD
X1
ANI
X0
OUT
Y1
Function
T0–159
Command code:
LD
X0
OR
X1
OUT
Y1
Function
T0–159
Command code:
LD
X0
ORI
X1
OUT
Y1
Function
N/A
Command code:
LD
X0
ORI
X2
LDI
X1
OR
X3
ANB
OUT
Y1
C0–C79
D0–D399
Description:
Load Contact a of X1
Create series connection
to contact b of X0
Drive Y1 coil
C0–C79
D0–D399
Description:
Load Contact a of X0
Create series connection
to contact a of X1
Drive Y1 coil
C0–C79
D0–D399
Description:
Load Contact a of X0
Create series connection
to contact b of X1
Drive Y1 coil
Description:
Load Contact a of X0
Establish parallel
connection to contact b of
X2
Load Contact b of X1
Establish parallel
connection to contact a of
X3
Series circuit block
Drive Y1 coil

Hide quick links: