Chapter 11 Summary of Parameter SettingsC2000-HS
10 Feedback Control Parameters
IM: Induction Motor; PM: Permanent Magnet Motor
NOTE
Pr.
Parameter Name
10-00
Encoder type selection
10-01
Encoder pulses per revolution
10-02
Encoder input type setting
Frequency division output
 10-03
setting (denominator)
 10-04
Electrical gear at load side A1
 10-05
Electrical gear at motor side B1
 10-06
Electrical gear at load side A2
 10-07
Electrical gear at motor side B2
Treatment for encoder / speed
 10-08
observer feedback fault
Detection time of encoder /
 10-09
speed observer feedback fault
Encoder / speed observer stall
 10-10
level
Detection time of encoder /
 10-11
speed observer stall
Encoder / speed observer stall
 10-12
action
Encoder / speed observer slip
 10-13
range
Setting Range
0: Disable
1: ABZ
2: ABZ (Delta encoder for Delta servo motor)
3: Resolver
4: ABZ / UVW
5: MI8 single phase pulse input
1–20000
0: Disable
1: Phases A and B are pulse inputs, forward direction if
A-phase leads B-phase by 90 degrees
2: Phases A and B are pulse inputs, forward direction if
B-phase leads A-phase by 90 degrees
3: Phase A is a pulse input and phase B is a direction
input (L = reverse direction, H = forward direction)
4: Phase A is a pulse input and phase B is a direction
input (L = forward direction, H = reverse direction)
5: Single-phase input
1–255
1–65535
1–65535
1–65535
1–65535
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
0.0–10.0 sec.
0: Disable
0–120%
0: No function
0.0–2.0 sec.
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
0–50%
0: No function
11-42
Default
0
600
0
1
100
100
100
100
2
1.0
115
0.1
2
50