Delta VFD300C43S-HS User Manual page 389

Vector control drive (high speed models)
Table of Contents

Advertisement

Operation Time of Fault Record 4 (Min.)
Settings
 If there is any malfunctions when the drive operates, Pr. 06-17–Pr. 06-22 records the
malfunctions, and Pr. 06-63–Pr. 06-70 records the operation time for four sequential malfunctions.
Check if there is any problem with the drive according to the interval of the recorded fault.
Example:
The first error: ocA occurs after motor drive operates for 1000 minutes.
The second error: ocd occurs after another 1000 minutes.
The third error: ocn occurs after another 1000 minutes.
The fourth error: ocA occurs after another 1000 minutes.
The fifth error: ocd occurs after another 1000 minutes.
The sixth error: ocn occurs after another 1000 minutes.
Then Pr.06-17–06-22 and Pr.06-63–06-70 are recorded as follows:
1
Pr.06-17
Pr.06-18
Pr.06-19
Pr.06-20
Pr.06-21
Pr.06-22
Pr.06-63
Pr.06-64
Pr.06-65
Pr.06-66
Pr.06-67
Pr.06-68
Pr.06-69
Pr.06-70
※By examining the time record, you can see that that the last fault (Pr.06-17) happened after the
drive ran for 4 days and 240 minutes.
Low Current Setting Level
Settings
Low Current Detection Time
Settings
0–1439 min.
st
fault
2
nd
fault
ocA
ocd
0
ocA
0
0
0
0
0
0
0
0
0
1
1000
560
0
0
0
1000
0
0
0
0
0
0
0
0
0.0–100.0 %
0.00–360.00 sec.
Chapter 12 Description of Parameter SettingsC2000-HS
3
rd
fault
4
th
fault
ocn
ocA
ocd
ocn
ocA
ocd
0
ocA
0
0
0
0
2
2
120
1120
1
2
560
120
0
1
1000
560
0
0
0
1000
12.1-06-23
Default: Read only
5
th
fault
6
th
fault
ocd
ocn
ocA
ocd
ocn
ocA
ocd
ocn
ocA
ocd
0
ocA
3
4
680
240
2
3
1120
680
2
2
120
1120
1
2
560
120
Default: 0.0
Default: 0.00