Delta VFD300C43S-HS User Manual page 488

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
Parameter
Pr.11-00
Pr.11-01
Pr.11-02
Pr.11-03
Pr.11-04
Pr.11-05
 PM FOC+PG With-load starting adjustment procedure
 With-load Operation Adjustment:
C1. Low-frequency load performance, when the drive operates under ASR1/ASR2 switch
frequency (Pr.11-02):
a. If the low-speed frequency cannot start-up with load or the rotor speed is not smooth,
increase Pr.11-03 (ASR1 low-speed bandwidth), or increase Pr.11-01 (Per-unit system
inertia).
b. If an oscillation or over current (oc) error occurs at low-speed frequency, decrease
Pr.11-03 (ASR1 low-speed bandwidth) or decrease Pr.11-01 (Per-unit system inertia).
Description
System control
Per unit of system inertia
ASR1/ASR2 switch frequency
(it is suggested to set the switch frequency higher than
Pr.10-39)
ASR1 low-speed bandwidth
ASR2 high-speed bandwidth
ASR zero-speed bandwidth
12.2-00-18
Default
0
256
7Hz
10Hz
10Hz
10Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents