ID No.
Display on LCM Keypad
19
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Phase loss of the input power
Single phase power input on a
three-phase model
The power voltage has changed
Loose wiring terminal of input
power
Check if the input cable of 3-phase
power is broken
The voltage of input power has
changed
Unbalance three-phase of the
input power
Warning Name
Phase loss
Input phase loss warning
(PHL)
Action and Reset
One of the phases outputs less than Pr. 06-47
Pr. 06-46
Pr. 06-45=0
0: Warn and keep operation
"Warning" automatically clears when the drive stops
After the drive stops
N/A
Verify wiring of the main circuit.
Use the model with voltage that matches the power.
If the power of main circuit works well, check if the MC of the main circuit is
broken.
Cycle the power after verifying the power is normal. If PHL still occurs, return to
the factory for repair.
Tighten the terminal screws with the torque listed in the user manual.
Make sure the wiring is correct.
Replace the broken part of the cable.
Check setting for Pr. 06-50 (Time for Input Phase Loss Detection) and Pr. 06-52
(Ripple of Input Phase Loss).
Check the status of 3-phase power.
13-9
Chapter 13 Warning CodesC2000-HS
Description
Corrective Actions