Delta VFD300C43S-HS User Manual page 541

Vector control drive (high speed models)
Table of Contents

Advertisement

ID No.
Display on LCM Keypad
64
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
When the transmitted packet from
CANopen master exceeds the
maximum allowable quantity in a
certain time
ID No.
Display on LCM Keypad
65
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Internal PLC transmits too much
SDO at once
Warning Name
CAN/M cycle time-out
CANopen Master cycle time-out
(PCCt)
Action and Reset
When the transmitted packet from CANopen master exceeds the maximum
allowable quantity in a certain time, the PCCt warning displays.
Immediately displays when the fault is detected
N/A
The warning automatically clears when changing the configuration and
re-executing the program.
N/A
N/A
Increase the time setting of D1090 synchronization cycle
Warning Name
CAN/M SDO over
CANopen Master SDO overflow
(PCSF)
Action and Reset
When the CANopen master transmits too much SDO that causes buffer
overflow, the PCSF warning displays
Immediately displays when the fault is detected
N/A
Cycle the power, or stop the PLC and run the PLC again
N/A
N/A
The PLC program needs to confirm receiving the SDO feedback data before
sending another SDO command.
13-29
Chapter 13 Warning CodesC2000-HS
Description
Corrective Actions
Description
Corrective Actions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents