Chapter 12 Description of Parameter SettingsC2000-HS
Multi-function Output 1 (AFM1)
Multi-function Output 2 (AFM2)
Settings
Function Chart
Settings
0
Output frequency (Hz)
1
Frequency command (Hz)
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC BUS Voltage
6
Power factor
7
Power
8
Output torque
9
AVI
10
ACI
11
AUI
12
Iq current command
13
Iq feedback value
14
Id current command
15
Id feedback value
18
Torque command
19
PG2 frequency command
20
CANopen analog output
21
RS-485 analog output
Communication card analog
22
output
23
Constant voltage output
CANopen and RS-485 analog
25
output
Analog Output Gain 1 (AFM1)
Analog Output Gain 2 (AFM2)
Settings
 Adjusts the voltage level outputted to the analog meter from the analog signal (Pr.03-20) output
terminal AFM of the drive.
0
25
Functions
0.0–500.0 %
12.1-03-18
Maximum frequency Pr. 01-00 is regarded as 100%.
Maximum frequency Pr. 01-00 is regarded as 100%.
Maximum frequency Pr. 01-00 is regarded as 100%.
(2.5 X rated current) is regarded as 100%
(2 X rated voltage) is regarded as 100%
450 V (900 V)=100%
-1.000
1.000=100%
(2 X rated power) is regarded as 100%
Full-load torque is regarded as 100%
0
10V = 0
100%
4
20mA = 0
100%
-10
10V=0
100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
Rated torque is regarded as 100%
Maximum frequency Pr. 01-00 is regarded as 100%.
CANopen communication analog output
For RS-485 (InnerCOM / MODBUS) control output
Communication analog output (CMC-MOD01,
CMC-EIP01, CMC-PN01, CMC-DN01)
Pr. 03-32 and Pr. 03-33 control voltage output level.
0
100 % of Pr. 03-32 corresponds to 0
For CANopen and InnerCOM control output
Default: 0
Default: 0
Descriptions
10 V of AFM1.
Default: 100.0
Default: 100.0