Delta VFD300C43S-HS User Manual page 440

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
10-01 and Pr. 10-02 are changed, cycle the power of the motor drive.
1. The speed formula is (input ppr) / (PG1 ppr), when PG1 ppt = 2500, PG2 is single-phase
input, and the input pps is 1000 (1000 pulse per second), the speed should be
(1000 / 2500) = 0.4Hz.
2. The same pps inputs of A/B phase pulse or single-phase pulse input should get the same
frequency command.
Frequency Division Output Setting (Denominator)
Settings
 Sets the denominator for the frequency division of the PG card feedback and output. When you
set it to 2 with feedback 1024 ppr, PG OUT (pulse output) of PG card is 1024 / 2 = 512 ppr.
Electrical Gear at Load Side A1
Electrical Gear at Motor Side B1
Electrical Gear at Load Side A2
Electrical Gear at Motor Side B2
Settings
 Use Pr. 10-04–Pr. 10-07 with the multi-function input terminal (set to 48) to switch to Pr.
10-04–Pr. 10-05 or Pr. 10-06–Pr. 10-07, as the following shows.
Treatment for Encoder / Speed Observer Feedback Fault
Settings
Detection Time of Encoder / Speed Observer Feedback Fault
Settings
 When there is an encoder loss, an encoder signal error, a pulse signal setting error or a signal
error, if the duration exceeds the detection time for the encoder feedback fault (Pr. 10-09), the
encoder signal error occurs. Refer to Pr. 10-08 for encoder feedback fault treatment.
1–255
1–65535
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
0.0–10.0 sec.
0: Disable
12.1-10-3
Default: 1
Default: 100
Default: 2
Default: 1.0