Delta VFD300C43S-HS User Manual page 616

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 15 CANopen Overview C2000-HS
15-3-2 DS402 Standard Control Mode
15-3-2-1 Related set up for an AC motor drive (following the DS402 standard)
If you want to use the DS402 standard to control the motor drive, follow these steps:
1.
Wire the hardware (refer to Section 15-2 Wiring for CANopen)
2.
Set the operation source: set Pr.00-21 to 3 for CANopen communication card control. (Run/
stop, forward/ reverse run...etc.)
3.
Set the frequency source: set Pr.00-20 to 6. Choose the source for the Frequency command
from the CANopen setting.
4.
Set the torque source: set Pr.11-33. Choose the source for the Torque command from the
CANopen setting.
5.
Set the position source: set Pr.11-40. Choose the source for the Position command from the
CANopen setting.
6.
Set DS402 for the control mode: Pr.09-40=1
7.
Set the CANopen station: set the CANopen station (range 1–127, 0 is the disable CANopen
slave function) with Pr.09-36. Note: set Pr.00-02 = 7 to reset if the station number error CAdE
or CANopen memory error CFrE appears.
8.
Set the CANopen baud rate: set Pr.09-37 (CANBUS Baud Rate: 1Mbps(0), 500Kbps(1),
250Kbps(2), 125Kbps(3), 100Kbps(4) and 50Kbps(5))
9.
Set the multiple input functions to Quick Stop. You can also choose enable or disable; the
default setting is disabled. If it is necessary to enable the function, set MI terminal to 53 in one
of the following parameters: Pr.02-01–Pr.02-08 or Pr.02-26–Pr.02-31. (Note: This function is
available in DS402 only.)
15-3-2-2 The status of the motor drive (by following DS402 standard)
According to the DS402 definition, the motor drive is divided into 3 blocks and 9 statuses as
described below.
3 blocks
1. Power Disable: without PWM output
2. Power Enable: with PWM output
3. Fault: One or more errors have occurred.
9 status
1. Start: Power On
2. Not ready to switch on: the motor drive is initiating.
3. Switch On Disable: occurs when the motor drive finishes initiating.
4. Ready to Switch On: warming up before running.
5. Switch On: the motor drive has the PWM output, but the reference command is not effective.
6. Operation Enable: able to control normally.
7. Quick Stop Active: when there is a Quick Stop request, stop running the motor drive.
8. Fault Reaction Active: the motor drive detects conditions that might trigger error(s).
9. Fault: One or more errors have occurred in the motor drive.