Chapter 12 Description of Parameter SettingsC2000-HS
2. PM FOC+PG Adjustment Procedure (※ the number marked on the procedure corresponds to
the number of following adjustment explanations)
 PM FOC+PG Motor Parameter Adjustment Procedure
1. AUE auto-tuning error
2. Measured resistance,
inductance or back
EMF error
1. If AUE offset angle tuning error occurs
2. If the measured angle continuously to
be 0 or 360 degree
a. Check if the red LED on PG card is ON
b. Check the connection of encoder
and PG card
PMFOC+PG
Adjustment Procedure
(PM parameters dynamic measuring)
Pr.10-02 Encoder input type setting =1
(PM pole origin dynamic measuring)
NO
1.Parameter Reset
Pr.00-02=10
2.Pr.05-33 Choose motor
=1(SPM) / 2(IPM)
3.Motor Parameter Setting
Pr01-01 額定頻率
Pr.01-01 Rated Frequency
額定電壓
Pr
Pr.01-02 Rated Voltage
滿載電流
Pr
Pr.05-34 Full-load Current
Pr
額定功率
Pr.05-35 Rated Power
Pr
額定轉速
Pr.05-36 Rated Rotor Speed
電機極數
Pr05
Pr.05-37 Motor Poles
4.Motor Parameter Auto Tuning
Pr.05-00=5
or Pr.05-00=13
(PM parameters static measuring)
Press RUN
Motor auto-tuning
successful?
NO
YES
5.Setting Encoder Parameter
Check the corresponding encoder
power and input PG card
Pr.10-00 Encoder type selection
Pr.10-01 Encoder pulse
6.Measure PM Pole Origin Angle
Pr.05-00=4
Press RUN
PM PG Offset Angle
Pr.05-42?
YES
7.Re-power after Power Off
12.2-00-12
Check Motor Parameters
Pr.05-39 Rs stator resistance
Pr.05-40 Permanent magnet
motor Ld
Pr.05-41 Permanent magnet
motor Lq
Pr.05-43 Ke parameter
PG Card Type:
EMC-PG01/02L
-
EMC-PG01/02O
EMC-PG01/02U
EMC-PG01R
It is suggested to measure
the offset angle more than
twice, to assure that the
angle tolerance is within ±5
degree.