Chapter 5 Main Circuit TerminalsC2000-HS
Frame E
If you install at Ta 50°C environment, please select copper wire with voltage rating 600V and
temperature resistant at 75°C or 90°C.
If you install at Ta 50°C above environment, please select copper wire with voltage rating 600V and
temperature resistant at 90°C or above.
For UL installation compliant, please use copper wires for installation, the wire gauge is based on
temperature resistant at 75°C which is requested and recommended from UL. Do not reduce the
wire gauge when using higher temperature wire.
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, -/DC-, +1/DC+
Model Name
Max. Wire
Gauge
120 mm
VFD1100C43A-HS
[4/0 AWG*2]
R/L1
S/L2
T/L3
Main Circuit Terminals
Min. Wire
Screw Spec. and
Gauge
Torque (±10%)
2
2
*2
95 mm
*2
[3/0 AWG*2]
[156.2 lb-in.]
U/T1
V/T2
Max. Wire
Gauge
M8
2
180 kg-cm
95 mm
*2
[3/0 AWG*2]
[17.65 Nm]
5-8
W/T3
Terminal
Min. Wire
Screw Spec. and
Gauge
Torque (±10%)
M8
2
95 mm
*2
180 kg-cm
[3/0 AWG*1]
[156.2 lb-in.]
[17.65Nm]