Vector control drive (high speed models)
Table of Contents

Advertisement

 TQC Sensorless (Pr. 00-13=2) control diagram is shown in the following:
Load Selection
Settings
 Normal duty: over-load rated output current 160% in 3 seconds (120%, 1 minute). Refer to Pr.
00-17 for the setting for the carrier wave. Refer to Pr. 00-01 or the specification table in Chapter
09 for the rated current.
 In Normal Duty, the default setting of Pr. 06-03 and Pr. 06-04 is 120%, and the maximum setting
range is 160%. However, if DC voltage is higher than 700V
145%.
Carrier Frequency
Settings
 This parameter determinates the PWM carrier frequency for the AC motor drive.
Model
VFD300–750C43A-HS
VFD1100C43A-HS
VFD1600C43A-HS
VFD2200C43A-HS
VFD3550C43A-HS
 From the table, you see that the PWM carrier frequency has significant influences on the
electromagnetic noise, the AC motor drive heat dissipation, and the motor acoustic noise.
0: Normal load
2–15 kHz
Settings
2–15kHz
2–15kHz
2–12kHz
2–10kHz
2–9kHz
12.1-00-11
Chapter 12 Description of Parameter SettingsC2000-HS
, then the maximum setting range is
DC
Default: Read only
Default: Table below
Default
10kHz
8kHz
8kHz
6kHz
6kHz