 No-load/ Light-load Running Adjustment
9. No-load trial run
Set the frequency command to 10Hz to proceed the encoder running test:
A1. If the motor starts in a reverse direction.
If the motor starts in a reverse direction, set the encoder input type Pr.10-02 = 2 (phases
A and B are pulse inputs, forward direction if B-phase leads A-phase by 90 degrees.)
A2. Observe if a PGFx error is displayed on the keypad, or the motor runs in an abnormal
speed.
If the PGFx error is displayed or the motor runs in an abnormal speed, refer to Section 14
"Fault Codes and Descriptions" or the following table for PGFx error type and further
treatment.
PGF Error (code)
PGF1 (42)
PGF2 (43)
PGF3 (44)
PGF4 (45)
PGF5 (65)
10. No-load / light-load running test
a. Set the speed regulator (ASR) as Pr.11-00=1, and set the ASR gain as auto-tuning.
b. Start the motor with no-load / light-load and proceed acceleration / deceleration test.
B1. Accelerate to the rated frequency and observe if the motor runs stably.
- If the output rotor speed cannot follow the acceleration time, increase Pr.11-04 (ASR2
high-speed bandwidth) or Pr.11-03 (ASR1 low-speed bandwidth).
- If a high-frequency oscillation occurs in the output frequency, decrease Pr.11-04 (ASR2
high-speed bandwidth) or Pr.11-03 (ASR1 low-speed bandwidth).
B2. Accelerate the motor to the maximum frequency and observe if it runs stably.
If an oscillation occurs or motor stalls at maximum rotor speed during operation, increase
Pr.11-04 (ASR2 high-speed bandwidth) or Pr.00-17 (Carrier frequency).
Setting curve of speed regulator (ASR) and related parameter:
Chapter 12 Description of Parameter SettingsC2000-HS
Description
PG feedback error
PG feedback loss
PG feedback stall
PG slip error
PG hardware error
12.2-00-17
Solution
Check parameter setting of Pr.10-00–10-02
Check the wiring of encoder and PG card
Check the wiring of encoder and PG card
Check the pulse setting of Pr.10-01
Check the wiring of encoder and PG card
Check if the PG card is installed on the correct
slot position
Check the setting parameter of the encoder